POWER TRANSFORMER
DAILY CHECKS & MAINTENANCE
- HT & LT Voltage and Current reading
- WTI & OTI Reading
- Oil level in conservator tank & OLTC tank
- Tap position & Tap changer counter reading
- PRV status & Buchholz relay status
- Condition of silica gel in breathers
- Cleanliness of transformer and accessories
- Visual leakage / seepage of oil
- Humming/any abnormal sound of transformer and accessories.
QUARTERLY CHECKS & MAINTENANCE
- Checking of OLTC mechanism Step by step
- Tightening of HV & LV connection
- Checking of gas collection in Buchholz relay & cleaning of glass cover
- Operation of tap changer from local and remote
- Condition check/replacement of silica gel
- Alarm/Tripping signal checking of OTI, WTI, Buchholz and PRV signal at panel.
- Testing of oil (BDV and Moisture content)
YEARLY CHECKS & MAINTENANCE
- Cleaning of Transformer
- Oil leakages checks for all joint & attend the leaks
- Inspection of CT JB and tightness the TB
- Inspection of transformer and replace the faulty components
- Testing of oil (DGA & IS-1866 characteristics)
- Painting of transformer (if peel off condition)
- Routine and special test on transformer