ARK Power Solutions Private Limited
"An ISO: 9001- 2015 Company"
- POWER TRANSFORMER
- AUXILIARY TRANSFORMER
- CURRENT TRANSFORMER
- POTENTIAL TRANSFORMER
- CIRCUIT BREAKER
- ISOLATOR
- LIGHTING ARRESTER
- POWER CABLE
- PROTECTION RELAYS
- AUXILIARY RELAYS
- METERS
- EARTH PITS
POWER TRANSFORMER
ANNUAL CHECKS & PREVENTIVE MAINTENANCE Internal Protections Check (WTI, OTI, Buchholz Relay, PRV & MOG) Insulation Resistance / Polarization Index Check (Digital IR Tester, Make: Megger, Model: BM5200) Magnetizing Current, Magnetic Balance, Voltage Ratio & Short Circuit Check Winding Resistance (TWRM, Make: SCOPE, Model: TRM104) Vector Group Check Capacitance & Tan Delta Measurement Test (Tan Delta, Make:Megger, Model: DELTA 4110) Oil Filtration until BDV is achieved (withstand 60 KV/min as per IS) EVERY FOUR YEARS OR WHEN SHIFTED Sweep Frequency Response Analysis (SFRA, Make:Megger, Model: FRAX 101) Oil Insulation Diagnostics Test (DIRANA, Make:Megger, Model: IDAX 300)